Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

be placed in a containment sump meeting the new performance standards?

0
Posted

be placed in a containment sump meeting the new performance standards?

0

Yes, the replacement STP will have to be placed in a containment sump meeting the requirements of the new performance standards including continuous interstitial monitoring using an electronic sump sensor or vacuum, pressure or hydrostatic interstitial monitoring methods. Question: To install a containment sump at the STP for an existing UST, I have to cut the pipe outside of the area where the containment sump will be located, install the sump, and then splice in a section of new pipe.