Can 60 Hz transformers be used on 50 Hz?
A. Yes. 60 Hz transformers can be used on 50 Hz if special precautions are taken. The change in frequency will impact the flux density of the transformer causing it to run hot, as if it were overloaded. To offset this effect, you must decrease the input voltage by approximately 17% (1/6th). This means that a transformer rated for a 480 Volt, 60 Hz input could run at 50 Hz but with a maximum input voltage of 398 volts. On the other hand, 50 Hz transformers can be run on 60 Hz with no ill effects.
Yes. 60 Hz transformers can be used on 50 Hz if special precautions are taken. The change in frequency will impact the flux density of the transformer causing it to run hot, as if it were overloaded. To offset this effect, you must decrease the input voltage by approximately 17% (1/6th). This means that a transformer rated for a 480 Volt, 60 Hz input could run at 50 Hz but with a maximum input voltage of 398 volts. On the other hand, 50 Hz transformers can be run on 60 Hz with no ill effects.