Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Can I replace a 2-pole breaker feeding two branch circuits with two 1-pole AFCI’s?

0
Posted

Can I replace a 2-pole breaker feeding two branch circuits with two 1-pole AFCI’s?

0

No. The most common reason for a 2-pole circuit breaker feeding two branch circuits is the use of multi-wire branch circuits, also known as shared neutral wiring. This means that the two branch circuits use the same neutral conductor as a current return path to the loadcenter or panelboard. In these cases, a 2-pole AFCI, such as the Siemens Q215AF, should be used to replace the 2 pole conventional breaker. Two 1-pole AFCI’s cannot be used with this wiring method. If separate neutral wires exist for both branch circuits, then two 1-pole AFCI’s can be used. Each branch circuit load conductor and its corresponding neutral conductor must be connected to the same AFCI for proper operation.