Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

How is the Reactive Capability data on the Resource Asset Registration Form (RARF) completed?

0
Posted

How is the Reactive Capability data on the Resource Asset Registration Form (RARF) completed?

0

All Reactive Curve data is to be entered as a Gross output. The following rules are to be used for inputting Reactive Curve data: – Must represent the full capacity of the reasonability limits; – MWs must be incremental to other relevant points on reactive capability curves; – Lead values are negative (include sign); – Lag values are positive (do not include sign); – All MW break points must have unique values; – 1st and 4th break points should extend from Unit Min Ouput (LRL) to Unit Max Output (HRL); – MW5 represents the MW output at Unity Power Factor (zero MVARs); – Lag values must be less than the Maximum Leading Operating Capability (MAXLAG); – Lead values must be less than the Maximum Lagging Operating Capability (MAXLEAD). Note: The whitepaper indicates MW1 on the Reactive Capability Curve must be the lowest seasonal LSL.