Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

I changed the thermocouple in the converter and the Temp controller is reading all LLLLs. What did i do wrong?

0
Posted

I changed the thermocouple in the converter and the Temp controller is reading all LLLLs. What did i do wrong?

0

LLLLs mean that the FUJI temp controller is reading too low a temperature and will not try and heat the converter. Typically this is set at 0 deg C as it leaves the factory. If the thermocouple wires are backwards it will essentially be reading a negative temp, -25 if room temp. So if the room is warm, the wires must be reversed.