Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

I have a specification that calls for bolt-on breakers. Can we use bolt-on breakers in the MSLC 341 Sequencing Load Center?

0
Posted

I have a specification that calls for bolt-on breakers. Can we use bolt-on breakers in the MSLC 341 Sequencing Load Center?

0

No. The load centers have insufficient room to accommodate bolt-on breakers. The bolt-on tabs require an additional inch between the two breaker rows. If bolt-on breakers are required use the MSP or MSPH Sequencing Panelboards. The MSPs will accept bolt-on or snap-in breakers. The MSLCs only accept snap-in breakers.