Is sensitivity testing of each smoke detector required on an addressable system?
All smoke detectors, whether addressable or not, are required to be sensitivity tested. Under NFPA 72 Chapter 10 Table 10.4.2.2 item g, test methods that are allowed include a calibrated test method, manufacturer’s calibrated sensitivity test instrument, listed control equipment arranged for the purpose, smoke detector/control unit arranged for the purpose, or other calibrated sensitivity test method approved by the Authority Having Jurisdiction (AHJ). Many of the newer addressable fire systems have the control equipment listed to automatically confirm the sensitivity of the smoke detectors. It’s advisable to check with your equipment manufacturer. Q: Do sprinkler gauges need to be replaced every 5 years? According to NFPA 25 Chapter 5.3.2 NFPA 2002 edition, “Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. Gauges not accurate to within 3 percent of the full scale shall be recalibrated or replaced.” The Water-Based Protection Systems
Related Questions
- A primer on selection, installation and testing. Which type of duct smoke detector is preferred for HVAC applications, photoelectric or ionization?
- I already have a battery-operated smoke detector, so why would I need one installed as part of my security system? Whats the difference?
- Does the air conditioning system smoke detector have to be wired into the building’s fire alarm system?