Must my kitchen cooking surface fire suppression system comply with U.L. 300?
The applicable rules of the Office of the State Fire Marshal (41 Ill. Adm. Code 251) reference NFPA standards that result in all newly installed cooking surface fire suppression systems needing to be tested and listed in accordance with UL 300. Furthermore, the rules require that existing cooking surface fire suppression systems be brought into compliance with UL 300 by January 1, 2010. (Systems located in governmental entities are allowed until January 1, 2011 to comply with a UL300 listed system). To date, all of the systems listed by UL in accordance with the UL 300 requirements have been wet-chemical systems. There are currently no dry chemical systems that are compliant with UL 300 listing criteria. Therefore, all new installations of systems for the protection of commercial kitchen cooking equipment must be wet-chemical systems and existing dry chemical suppression systems must be replaced by UL 300 compliant wet chemical systems by January 1, 2010 (or January 1, 2011 if within a