Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

The Reactance Multiplying Factor (RMF) is read from table 4 (?

0
Posted

The Reactance Multiplying Factor (RMF) is read from table 4 (?

0

The total short circuit capacity available is This current is the same magnitude with an X/R ratio equal to 4.899 (HV Bus 1), 10 (HV Bus 2) or 999 (HV Bus 3). We must now adjust for the X/R ratio. The test X/R ratio for this type of equipment is 15, see Table 1. Therefore, we do not adjust for breakers 52-1 or 52-2. However we must adjust for breaker 52-3. From Table 6 for an X/R ratio of 999 we can read for a 3-cycle breaker a MF of 1.35. Note, the table only goes up to an X/R of 130. This matches the results of the Equipment Evaluation and the SC.rpt file. Example 9 A co-worker has brought you the following single line diagram. The client he is working for is coming into the office for a review meeting. He would like you to quickly pop his proposed system into PTW and tell him what short circuit ratings are required for the SWBD and 2 panels. – There is no charge number for this assignment. – Make assumptions for missing data! – His last request is that since there are so many unknow