Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What is the farthest I can run the exhaust/cooling ducts? Can I block one duct on CP units?

0
Posted

What is the farthest I can run the exhaust/cooling ducts? Can I block one duct on CP units?

0

Varies, depends on models (See Specifications: Click the following link to view the specifications- http://www.movincool.com/downloads/overview_specs.pdf). Length specified is total length in and out of unit. For condenser plenum, 10’ inlet and 10’ outlet = 20 total feet. Each 90 deg bend = approx 8’-10’ of duct. Blocking one duct is not recommended. Too much static pressure can build up and the unit will shut down.