What is the purpose of the Equipment Evaluation Study module?
– To compare distribution equipment ratings to the results of the Demand Load Study module. – To compare distribution equipment ratings to the results of the Load Flow Study module. – To compare distribution equipment ratings to the results of the Short Circuit Study module. As long as available fault duty X/R ratios are at or below rated equipment X/R ratios the Short Circuit Study module results will match Equipment Evaluation Study module results. – To convert fault duties to the equipment X/R ratio base if the available fault duty X/R ratio is greater than the equipment rated X/R ratio. In this case the Short Circuit Study module results will not match the Equipment Evaluation Study module results.