Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What Is The Required Clearance In Front Of Electrical Panels?

clearance electrical Panels
0
Posted

What Is The Required Clearance In Front Of Electrical Panels?

0

These come out of the Oregon Fire Code Book. If this doesn’t fully answer your question, please contact our Fire Prevention Office through our website HERE. Oregon Fire Code 605.3 (Working Space And Clearance) A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.