Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What metal gauge do we need to specify when employing Vermiduct as a Fire upgrading system?

0
Posted

What metal gauge do we need to specify when employing Vermiduct as a Fire upgrading system?

0

For Kitchen Exhaust ductwork, AS 1668.1 requires the sheet metal to be of 1.2 mm gauge. With ‘Vermiduct’ 1.0 mm sheet metal is all that is required for ductwork up to 4.8 m wide x 3 m deep. In some special cases ducting not exceeding 1200 mm x 1200 mm may be constructed from .8 mm sheet metal. Please note however that in some cases (ie high pressure ducts etc) greater metal thickness may be warranted! Refer to LAF for further details.