When should a DYNASTY VRLA battery be given a freshening charge?
The term “freshening charge” usually relates to periodic charging of batteries that are in inventory or storage. Twelve-volt DYNASTY VRLA batteries should be given a freshening charge at 2.4 volts per cell average for 12 hours when their open circuit voltage declines to an average of 2.08 volts per cell.