Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Where and how should a remote acting fire valve be installed?

acting installed remote valve
0
Posted

Where and how should a remote acting fire valve be installed?

0

A remote acting fire valve should be installed with the sensor inside the appliance casing and the valve body external to the building as per British Standard 5410: Part 1: 1997 (see OFTEC Technical Book 3 2010) so that in the event of a fire or an over heat situation at the appliance, the oil is isolated external to the building. For externally installed appliances, the fire valve cut off point should be located a minimum of 1m from the appliance.