Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Obstacles (§ 2.2.5) – fire hose bags Q – Do fabric or canvas hose bags, as part of a fire hose assembly, require horizontal photoluminescent markings?

0
Posted

Obstacles (§ 2.2.5) – fire hose bags Q – Do fabric or canvas hose bags, as part of a fire hose assembly, require horizontal photoluminescent markings?

0

A – If the hose bags project more than 4″ into the egress path, then bags require obstacle markings per § 2.2.5. Interestingly, we have been told by many installers that they have chosen to place bags on the hoses to make it easier to install the PL obstacle markings, because the UL listing plate would otherwise be the only location on which to place the markings, and placing the markings on the UL plate would invalidate the hose apparatus’ listing.