Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Can the DL05 communicate with other DirectLogic PLCs?

Communicate dl05 plcs
0
Posted

Can the DL05 communicate with other DirectLogic PLCs?

0

Yes, the DL05 can communicate to all of the other DirectLogic PLCs including the DL06, DL105, DL205, DL305 and DL405 families. The DL05 can be a serial master or slave to a DL06 (DirectNet or Modbus RTU), D2-240 (DirectNet)D2-250-1(DirectNet or Modbus RTU), D2-260 (DirectNet or Modbus RTU), D3-340 (DirectNet), D3-350 (DirectNet or Modbus RTU), D4-440 (DirectNet), and D4-450 (DirectNet or Modbus RTU). It can also be an Ethernet master or slave when using an optional Ethernet Communications Module in the option slot of the DL05. An RS232 to RS422/485 converter will be required for communications wiring.