Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Can the inputs of an FCPS-24F be activated by a NAC circuit that has a System Sensor MDL module on it?

0
Posted

Can the inputs of an FCPS-24F be activated by a NAC circuit that has a System Sensor MDL module on it?

0

Yes, but the Synch signal will not be transferred from the inputs of the FCPS-24F to the outputs so the FCPS-24F NACs will not be synchronized. Furthermore, some distortion of the audible signal may occur, particularly with a steady DC NAC signal. For full synchronization, install a slave MDL module on the outputs of the FCPS-24 and synchronize it with a master MDL module. However, do not daisy-chain the FCPS-24F outputs in this case. Note: The inputs on the FCPS-24F can be activated by 9-32 VDC filtered or unfiltered. Alternately, consider the FCPS-2404 (4 amp/1 NAC) which will transparently transfer a synchronized signal from an MDL module though to its output.