How do I set the PID Loop to receive a reset schedule set point?
To setup Active PID control, you must configure the following parameters. P0756 defines the analog input type for the actual value. Index 0 is analog input 1 and index 1 is analog input 2. Use a value of 0 for 0-10 V, a 2 for 0-20mA and a 5 for the Ni 1000 sensor.P0757 sets the minimum scaling of the sensor type. Use a 0 for 0-10 V, a 4 for 4-20 mA, or a 20 for the Ni 1000 sensor.P0758 sets the minimum scaling for the sensor range, if you are using a Setra with a range of -2.5 to 2.5 then the value entered in this parameter will be -2.5.P0759 sets the max scaling range of the sensor type. Use a 10 for 0-10 V, a 20 for 4-20 mA, or a 120 for the Ni 1000 sensor.P0760 sets the max scaling for the sensor range, again if you are using a Setra with a range of -2.5 to 2.5 then the value entered in this parameter will be 2.5When wiring a 0-10v or 4-20 mA Analog Input devices, like a Static Pressure Sensor. The following diagram should be used. Make sure that the appropriate setting (voltage or