Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Is there any configuration necessary to get the ECOM100 to talk Modbus TCP?

0
10 Posted

Is there any configuration necessary to get the ECOM100 to talk Modbus TCP?

0
10

This depends. If you are going to use the ECOM100 as a Modbus TCP server (slave), then there is no configuration necessary (except for the normal IP Address). However, if you plan on using the ECOM100 as a Modbus TCP client (master), then you have to configure the Peer-to-Peer parameters. This is done using NetEdit3 (right-click on ECOM100, select Peer To Peer Configuration), or an HTML Browser (select Peer to Peer).