Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

What is the different application for interface TCP/IP, RS-232/422/485 for Pongee Access Controller?

0
10 Posted

What is the different application for interface TCP/IP, RS-232/422/485 for Pongee Access Controller?

0
10

(a). TCP/IP : No distance limitation between the Access Controller and PC (running Pegasus PGAccess), anywhere there is RJ-45 interface of Ethernet HUB or Router in the worldwide, connects to numerous Pongee Access Controllers at the same time. (b). RS- 232 : Distance limitation is 15 meters between the Access Controller and PC, connects up to 7~8 sets Pongee Access Controllers at the same time. (c). RS- 422 : Full-duplex communication, distance limitation is 1,200 meters between the Access Controller and PC, connects up to 160 sets Access Controllers thru Pongee Multi-channel converter PCP832-16 at the same time. (d). RS- 485 : Half-duplex communication, distance limitation is 1,200 meters between the Access Controller and PC, connects up to 32 sets Access Controllers thru Pongee RS485/232 Converter at the same time.