What is the minimum recommended requirements for inspection and testing of Protectowire Linear Heat Detector?
The Protectowire Company recommends visual inspection of Protectowire Linear Heat Detector semi-annually. Do not heat test. The following tests should be performed annually: Test mechanically and electrically for function, measure and record loop resistance and investigate deviations from the acceptance test. Click here to go to our Protectowire products page where you will find installation guides containing information on testing Protectowire Linear Heat Detector.