Important Notice: Our web hosting provider recently started charging us for additional visits, which was unexpected. In response, we're seeking donations. Depending on the situation, we may explore different monetization options for our Community and Expert Contributors. It's crucial to provide more returns for their expertise and offer more Expert Validated Answers or AI Validated Answers. Learn more about our hosting issue here.

Where in the cable route should the barrier strip in Intrinsically Safe applications be located?

0
Posted

Where in the cable route should the barrier strip in Intrinsically Safe applications be located?

0

The barrier strip should be located outside the hazardous area and mounted near the junction box, multiplexer, or monitoring system. When using single barrier strips, the common signal carrier is grounded to the barrier enclosure; and therefore, must be in close proximity to monitor ground to prevent ground loops.

Related Questions

What is your question?

*Sadly, we had to bring back ads too. Hopefully more targeted.